CONFIGURING THE METER

Read this section for step-by-step procedures on configuring your meter. For a summary of menu configurations, refer to Table 6-1. Some menu items do not display if your meter does not have analog output or dual relay output capabilities. These menu items are noted accordingly in the following sub- sections. Factory defaults are in bold and italics.

SELECTING THE INPUT TYPE ("INPT")
To select your appropriate input type signal, follow these steps:

1. Press the MENU button. The meter shows "INPT".

2. Press the /MIN button. The meter flashes one of the following (default is 4004):
* "4004" = 44004
* "4005" = 44005
* "4006" = 44006
* "4007" = 44007
* "4008" = 44008
* "4016" = 44016
* "4018" = 44018
* "700" = Linear 3-Wire

3. Press the /MAX button to scroll through available choices.

4. Press the MENU button to store your selection. The meter momentarily shows "STRD", followed by "DEC.P" (Decimal Point).


SELECTING A DECIMAL POINT POSITION ("DEC.P")
To select a decimal point display position.

1. Press the MENU button until the meter shows "DEC.P"

2. Press the /MIN button. The meter shows one of the following:
    * FFFF. (default)
    * FFF.F
    * FF.FF
3. Press the /MAX button to scroll between available choices.

4. Press the MENU button to store your choice. The meter momentarily shows "STRD", followed by the next menu "RD.C.F" (Reading Configuration).

NOTE: When you change the decimal position the meter adjusts setpoint values and setpoint deadbands. These adjustments are made according to the new decimal point. If one or more of these values overflow, the meter flashes "ER2" when you store new decimal point position value.

USING READING CONFIGURATION ("RD.CF")
To select if the meter shows in Fahrenheit or Celsius, follow these steps:
1. Press the MENU button until "RD.CF" displays.

2. Press the /MIN button. The meter shows one of the following:
* "R.1=F" Fahrenheit - Default
* "R.1=C" Celsius

3. Press the /MAX button to toggle between available selections.

4. Press the MENU button to store your choice. The meter momentarily shows "STRD", followed by "S1.CF" (Setpoint 1 Configuration)

USING SETPOINT 1 CONFIGURATION ("S1.CF")
Setpoint 1 Configurations display only if your meter has dual relay output capabilities. You may use Setpoint 1 Configuration ("S1.CF") for the following:
    * To set setpoint 1's active band above or below your chosen value
    * To select whether setpoint 1's operation is latched or unlatched
Setting Setpoint 1's Active Band
1. Press the MENU button until the meter shows "S1.CF".

2. Press the /MIN button. The meter shows one of the following:
    *"S.1=A" (Active above the deadband) (default)
    * "S.1=B" (Active below the deadband)
3. Press the //MAX button to toggle between available choices.

4. Press the /MIN button to select if Setpoint 1 is latched or unlatched or press the MENU button to store your selection and enter "S2.CF" (Setpoint 2 Configuration)

Selecting if Setpoint 1 is Latched or Unlatched
1. Press the /MIN button. The meter shows one of the following:
    * "S.2=L" (setpoint 1 to be latched) (default)
    * "S.2=U" (setpoint 1 to be unlatched)
2. Press the //MAX button to toggle between available choices.

3. Press the MENU button to store your choice(s). The meter momentarily shows "STRD", followed by "S2.CF" (Setpoint 2 Configuration).

USING SETPOINT 2 CONFIGURATION ("S2.CF")
Setpoint 2 Configurations display only if your meter has dual relay output capabilities. You may use Setpoint 2 Configuration ("S2.CF") for the following:
    * To set setpoint's 2's active band above or below your chosen value
    * To select whether the setpoint 2's operation is latched or unlatched

Setting Setpoint 2's Active Band
1. Press the MENU button until the meter shows "S2.CF".


2. Press the /MIN button. The meter shows one of the following:

    * "S.1=A" (Active above the deadband) (default)
    * "S.1=B" (Active below the deadband)
3. Press the //MAX button to toggle between available choices.

4. Press the /MIN button to select if setpoint 1 is latched or unlatched or press the MENU button to store your selection and enter "S1.DB" (Setpoint 1 Deadband).

Selecting if Setpoint 2 is Latched or Unlatched
1. Press the /MIN button. The meter shows one of the following:
    * "S.2=L" setpoint 1 to be latche - default
    * "S.2=U" setpoint 1 to be unlatched
2. Press the
/MAX button to toggle between available choices.

3. Press the MENU button to store your selection(s). The meter momentarily shows "STRD", followed by "S1.DB" (Setpoint 1 Deadband).

SETTING THE SETPOINT 1 DEADBAND ("S1.DB")
Setpoint 1 Deadband displays only if your meter has dual relay output capabilities.
Factory default deadband is 003. To change the deadband (hysteresis) of setpoint 1, follow these steps:

1. Press the MENU button until the meter shows "S1.DB".

2. Press the /MIN button. The meter shows the last previously stored 4-digit number (0000 through 9999) with flashing 4th digit.

3. Press the
/MAX button to change the value of the flashing digit. If you continue to press the /MAX button, the flashing digit's value continues to change.

4. Press the /MIN button to scroll horizontally to the next digit.

5. Press the MENU button to store your selection. The meter momentarily shows "STRD", followed by "S2.DB" (Setpoint 2 Deadband).


SETTING THE SETPOINT 2 DEADBAND ("S2.DB")

Setpoint 2 Deadband displays only if your meter has dual relay output capabilities. Factory default deadband is 003. To change the deadband (hysteresis) of setpoint 2, follow these steps:


1. Press the MENU button until the meter shows "S2.DB".

2. Press the /MIN button. The meter shows the last stored number (0000 through 9999) with flashing 4th digit.

3. Press the
/MAX button to change the value of the flashing digit. If you continue to press the /MAX button, the flashing digit's value continues to change.

4. Press the
/MIN button to scroll to the next digit.

5. Press the MENU button to store your selection. The meter momentarily shows "STRD" , followed by "OT.CF" (Output Configuration).

USING OUTPUT CONFIGURATION ("OT.CF")

Output Configuration displays only if your meter has analog output capabilities. Use Output Configuration ("OT.CF") to select the following:

* To enable or disable the analog output
* To determine if the analog output is current or voltage

Enabling or Disabling the Analog Output
To enable or disable the analog output.

1.
Press the MENU button until the meter shows "OT.CF".

2. Press the /MIN button. The meter shows one of the following:
* "O.1=D" Analog output disabled
* "O.1=E" Analog output enabled - default

3. Press the /MAX button to toggle between available choices.

4. Press the /MIN button to select analog output as current/voltage or press the MENU button to store your selection (the meter momentarily shows "STRD", followed by "OT.S.O", Output Scale and Offset - refer to Section 4.11)..


SELECTING ANALOG OUTPUT as CURRENT or VOLTAGE
Remember that Output Configuration displays only if your meter has analog output capabilities.

1.
Press the /MIN button. The meter shows one of the following:
* "O.2=V" Analog output = voltage
* "O.2=C" Analog output = current - default

2. Press the /MAX button to toggle between available choices.

3. Press the /MIN button to go back to selecting analog output as enabled or disabled or press the MENU button to store your choices (the meter momentarily shows "STRD", followed by "OT.S.O", Output Scale and Offset).